Water treatment comparison; of Using Dissolved Air Flotation Technology on a FPP (Further Poultry Processing) Plant in Victoria Operation With and Without Chemicals

Location
Victoria

Background

Wastewater generated from poultry further processing contains high levels of fats, solids and potentially starch, resulting in fairly high BOD. Depending on the production and cleaning cycles, concentrations and flows vary considerably.

Ingham’s FPP plant at Thomastown used to discharge wastewater flows in excess of 500KL/day to sewer via a grease trap. Naturally, with such a process, the quality of the wastewater being discharged to sewer was unacceptable.

Trials were conducted treating samples of wastewater with and without chemicals. The results are shown in the performance table below.

Process

The overall wastewater process involved mechanical screening to remove large solids to 1mm, followed by balancing.

The balance tank in this case was sized to hold 70% of one day’s production to allow for effective equalisation of flow and waste concentrations.

The wastewater was pumped from the balance tank to the DAF at a constant rate.

The DAF system was designed to accept chemicals for possible future requirements or recycling opportunities. The sludge removed from the DAF system is dewatered in a belt press.

Performance

Since the initial start up of the plant, the system has operated trouble free with excellent results.

Analyte Raw Water Without Chemicals With Chemicals
BOD 3000–8000 mg/L 30–50% reduction 70–90% reduction
SS 1500–6000 mg/L 60–75% reduction 95–99% reduction
O&G 100–1500 mg/L 60–80% reduction 96–99% reduction

See more about Tasman Waters manufacturing water treatment options

poultry case study Australia 2
poultry case study Australia

SERVICES

Glass laboratory chemical test in lab room

Chemical Treatment

FIND OUT MORE
Glass laboratory chemical test in lab room

Raw Water Intake

FIND OUT MORE
Glass laboratory chemical test in lab room

FGD Wastewater Treatment

FIND OUT MORE
Glass laboratory chemical test in lab room

Media Filtration

FIND OUT MORE
Glass laboratory chemical test in lab room

Sludge Handling

FIND OUT MORE
Glass laboratory chemical test in lab room

Water Pumps

FIND OUT MORE
Jones and Attwood
EnviroDAF Tech
Eimco Water Technologies
Copa Limited
Brackett Green
AJM Environmental Services
Tasman Water Technologies logo

Contact

27A Sleigh Place
Rd Wetherill Park NSW 2164

Other Offices

24/55 Commerce Circuit,
Yatala, QLD, 4207
Unit 13/38 Tikalara St,
Regency Park SA 5010
All Content Copyright © 2026 Tasman Water Technologies. Website Design Gold Coast by Shared Marketing